Electrical receptacle stopped working?
15amp electrical receptacle stopped working after plugging in a power tool. The power tool sparked, I turned it off, unpluged it. Other electrical devices do not work in the outlet. No breakers appears to have been tripped and I do not know which breaker corresponds to this receptacle. Not a gfi / gfci receptacle but it is in a hallway outside the bathroom.
other oultets and lights in hallway near this abd receptacle all work
basic electric meter - kind with 2 metal tips and light bulb shows no power from the wires?
bought a new receptacle, same as old one and plan to reinstall it but is this the issue or am I looking at a larger issue?
I do not understand what you mean by looking at other recetacles. I have checked the other rooms and all seems to work.
The bad recetacle had 3 wires - a white, black and brass (ground)
Well...
Your power tool shorted. All your other receptacles and lights work (I'm guessing that includes the GFCI in the bathroom) - so that should rule out tripped breakers or GFCI's. The problem should be fairly close to where the fault occurred. Check to see if there is power in the outlet box for your receptacle.
Turn the power off first. If your not sure which breaker it is, turn off the main breaker. Remove the receptacle. Disconnect the wires from the receptacle. Pull them out so that they stick out of the box and separate them. Turn the power back on and check to see if there is power. Check both, black to ground and black to neutral. If there is power there, then turn off your breaker again and install your replacement receptacle.
If there is no power there, then you should start by checking the outlets closest to this receptacle (don't forget to look on the other side of the wall for receptacles there). If your circuits were wired by using the "quick-wire" connections on the receptacles, these connections can be very weak and can easily burn out on a small arc.
Turn the power off again. Pull out the closest receptacle. If you have two or more cables coming into the receptacle, one of them might feed to your non-working receptacle. Disconnect the wires and visually check them to see if there are any noticeable burn marks on the wires. Twist the wires together (all blacks together, all whites together). Turn the power back on and check to see if your receptacle is working. You can repeat this, working your way out from the origin, until you find the problem.
If you can't locate the problem using this method, you should call an electrical contractor.
Items Recently Purchased From This Site:
ELECTRICAL RECEPTACLE TESTER AC OUTLET PLUG 3 PRONG GND NSI GFCI TES 122, 10 New TayMac In Use Wet Receptacle Outlet Covers GFCI, (25) Tamper Resistant GFCI Outlet Receptacle 15 amp White Child proof UL TR , (25) Tamper Resistant GFCI Outlet Receptacle 15 Amp 125V White LED 2008 UL TR , 400-030 — Electrical Receptacle Tester for GFCI Outlets, Case of 15 Leviton 7899-3W GFCI Receptacle 20 Amp Outlet , Case of 30 Leviton 7899-3W GFCI Receptacle 20 Amp Outlet , (25) Tamper Resistant GFCI Outlet Receptacle 20 Amp 125V White LED 2008 UL TR , NEW (20) GFCI Outlet Receptacle 15 Amp IVORY w/LED 2008, NEW (50) GFCI Outlet Receptacle 15 Amp IVORY w/LED 2008, NEW (5) GFCI Outlet Receptacle 15 Amp IVORY w/LED 2008, GFCI Electric Outlet Plug Receptacle Circuit Tester ideal for home Electrical, (10) Tamper Resistant GFCI Outlet Receptacle 20 Amp 125V White LED 2008 UL TR , (50) Tamper Resistant GFCI Outlet Receptacle 15 Amp 125V White LED 2008 UL TR , (5) Tamper Resistant GFCI Outlet Receptacle 20 Amp White LED 2008 UL NEW CODE!, (10) Tamper Resistant GFCI Outlet Receptacle 15A White LED UL TR Child proof , (3) Tamper Resistant GFCI Outlet Receptacle 15 Amp 125V White LED 2008 UL TR , LOT of 4 == 5-20R GFCI Dual-Outlet Receptacle Power == COOPER Wiring XGF20W-C, Leviton Combination Smartlock GFCI Switch Power Outlet Receptacle 8299 Lot 2, GFCI RECEPTACLE 1 CASE WHITE. 2 OUTLET W/COVER PLATE WSI ELECTRIC 15 AMP 110 V., (5) Tamper Resistant GFCI Outlet Receptacle 15 Amp 125V White LED 2008 UL TR , (1) Tamper Resistant GFCI Outlet Receptacle 15 Amp 125V White LED 2008 UL TR , (1) Tamper Resistant GFCI Outlet Receptacle 20 Amp 125V White LED 2008 UL TR , (10) Tamper Resistant GFCI Outlet Receptacle 15 Amp 125V White LED 2008 UL TR , (10) Cooper Eagle GFCI Outlet Receptacle LED 15 Amp GF15B Brown 15A LOT, (5) Tamper Resistant GFCI Outlet Receptacle 20 Amp 125V White LED 2008 UL TR , NEW Gfci/receptacle Outlet Cover Ea. Weatherproof Covers E98GFCN-CAR, Leviton SmartLockPro GFCI Receptacle Outlet 15A-125V w/ ScrewlessWallplate White, GFCI Electric Outlet Plug Receptacle Tester Circuit Analyzer Home Electrical, Pass & Seymour GFCI 20 Amp Beige Receptacle Outlet, 4~NW LEVITON SMARTLOCKPRO MOD#7899-I(IVORY)GFCI OUTLET/RECEPTACLE W/WALLPLATE{JS, Qty 4 Cooper GFCI Receptacle Outlet 15A / 20A Aspire , Leviton GFCI Polarity Circuit Tester for GFI Outlet Receptacle, White 20A Tamper Resistant GFCI Receptacle/Outlet (3), White GFCI Duplex Receptacle/Outlet 20 amp lot of 3, White GFCI Duplex Receptacle/Outlet 15 amp Lot of 3, Combination Home 125V GFCI - Outlet Receptacle Tester, 100 LOT LEVITON GFCI GFI OUTLET 7599-A ALMOND receptacle WITH MATCHING WALLPLATE, 100 lot LEVITON GFCI GFI OUTLET Duplex receptacle OUTLETS NEW, Cooper Wiring Devices VGF20V 20A Duplex Outlets GFCI Receptacle with Plate Ivory, 15 Amp GFCI Outlet Receptacle White W/Light 2008 , LEVITON GFCI GFI OUTLET 7599-A ALMOND Receptacle SmartlockPro Wallplate Includ , 2 pcs15 Amp GFCI Outlet Receptacle White W/Light 2008 , GFCI GFI UL2008 Tamper Resistant Outlet Receptacle 10PK, GFCI GFI UL2008 Tamper Resistant Outlet Receptacle 10PK, GFCI GFI UL2008 Tamper Resistant Outlet Receptacle 10PK, GFCI GFI UL2008 Tamper Resistant Outlet Receptacle 10PK, (10) GFCI GFI UL 2008 15 A & 20 A Outlet Receptacle, (10) GFCI GFI UL 2008 15 A & 20 A Outlet Receptacle, (10) GFCI GFI UL 2008 15 A & 20 A Outlet Receptacle,