Generator Transfer Switch
Installing a house generator. Can anyone tell me a little about the automatic transfer switch. install?
I have everything connected except for the transfer switch to the house. I just want to make sure I am doing this correctly.
What kind of automatic transfer switch do you have? Does it have a built-in loadcenter (panel)? Is it a weatherproof one with a built-in main breaker?
Depending on the brand of generator that you have, this will probably not be a DIY project. Generac generators comes with very good DIY installation instructions for their 7kW - 16kW generators. They prefer to have their larger generators installed by a professional.
If your transfer switch has a built-in loadcenter (panel), I recommend installing it right next to your existing breaker box. You need to install a conduit between your transfer switch and generator. In this conduit, you will run your 2 - hots, 1-neutral and 1-ground for the power from the generator. Additionally, depending on the requirements, you need to install a minimum of 2 conductors that sense utility power and allow the generator to start.
The conduit size depends on the size of wire and number of conductors in the conduit. The wire size is determined from the generator size. All of these specifications should be in your installation instructions.
You also need to install a conduit between your transfer switch and existing breaker box. In this conduit, you need the utility power to feed the transfer switch and the circuits that you want your generator to control during an outage. These circuits are already in your existing breaker box, you just need to transfer them into your transfer switch.
Don't forget to ground your generator. The instructions will have the specifications for grounding. Typically, you need to drive an 8' x 5/8" ground rod next to the generator and connect a #6 bare copper wire between the ground rod and a lug provided on the generator's frame.
As I mentioned earlier, this is not really a DIY project. If you are unsure of any of the steps involved, I highly recommend hiring a licensed electrician. If you are going to do this yourself, definately get an inspection when you are done, just to be sure.
Be sure to check with your local building codes to see if they have any additional requirements. I also recommend getting the 2005 edition of the NEC and read Article 445.
If you need further assistance, please visit -
http://electricalblog.gilchrist-electric.com
Items Recently Purchased From This Site:
TRANSFER SWITCH KIT for Portable Generators - 30 Amp - 120/240V - 6 Circuit, STANDBY GENERATOR - Residential - 8,000 Watt - NG & LP - Incl Transfer Switch, Generac 200 Amp RTS Transfer Switch for 60kW Generators RTSD200A3 NEW, Onan 150Amp 208V Generator ATS Automatic Transfer Switch - Worwetz Energy, Generac Guardian Air-Cooled 20kW Generator w/ RTS Transfer Switch 5875 NEW, RELIANCE CONTROLS PORTABLE GENERATOR POWER TRANSFER SWITCH KIT 30216BRK NEW, 5000 Watt 5KW Propane / Nat. Gas Home Standby Generator, CARB w/ Transfer Switch, Reliance Generator Transfer Switch-Single Circuit 7500W #CSR302, Generac GenReady Load Transfer Switch GIBSON ELECTRIC 740-670-2101 Generators, SQUARE D 200 Amp Breaker KAL26200WB8041 generator transfer switch, SQUARE D 100 Amp Breaker KAL26100WB8041 generator transfer switch, SQUARE D 100 / 200 AMP Transfer Switch Breaker Interlock 120 240 volt Generator, 50 amp Generator transfer switch rainproof power inlet box for generator cords, TRANSFER SWITCH for Portable Generators - 50 Amp - 120/240V - 10 Circuit, STANDBY GENERATOR - Residential - 7,000 Watt - NG & LP - Incl Transfer Switch, emergen switch / manual generator transfer switch, BRAND NEW RELIANCE CONTROLS PORTABLE GENERATOR POWER TRANSFER SWITCH KIT 3006HDK, TRANSFER SWITCH - Generator, 30 AMP, 6 Circuts.up to 7500 watts, pre-wired, NEW, SQUARE D QO1DM10030TRBR 100A Load Center for Generator Transfer Switch, STOP BRAKE SWITCH 50 Amp FOR WIND TURBINE GENERATOR LOAD TRANSFER SWITCH SOLAR, KOHLER 40 KW Generator 45R061 Electric Plant with Transfer Switch, Diesel 120V, STANDBY GENERATOR - Residential - 14,000 Watt - NG & LP - Incl Transfer Switch, Generac Generator 10kw With Auto Transfer Switch, USED 16kw Generac Guardian Generator with Transfer Switch and Load Center. NG/LP, Military Generator transfer switch , STANDBY GENERATOR - Residential - 17,000 Watt - NG & LP - Incl Transfer Switch, STANDBY GENERATOR - Residential - 10,000 Watt - NG & LP - Incl Transfer Switch, 2005 Asco 7000 Series Automatic Generator Transfer Switch in MS NO RESERVE, Evergood 100 Amp Generator Transfer Switch, Reliance Controls 31406CRK Pro/Tran 6-Circuit 30 Amp Generator Transfer Switch K, Generac 200 Amp RTS Transfer Switch, Generators Up To 60 kW RTSX200A3 NEW, Generac 100 Amp Automatic Transfer Switch 120/208 3 Phase for Generator, STANDBY GENERATOR - Residential - 20,000 Watt - NG & LP - Incl Transfer Switch, Generator Transfer Switch, Cutler Hammer CH series. Transfer Panel, 2002 Cummins Diesel Generator and Transfer Switch Set plus fuel tank and muffler, Reliance Controls TCA1006D Panel/Link Generator Transfer Switch, TRANSFER SWITCH for Portable Generators - 30 Amp - 120/240V - 8 Circuit, STANDBY GENERATOR - Residential - 17,000 Watt - NG & LP - Incl Transfer Switch, Automatic Transfer Switch for RV generator, for repair or parts, STOP BRAKE SWITCH 50 Amp FOR WIND TURBINE GENERATOR LOAD TRANSFER SWITCH SOLAR, STANDBY GENERATOR - Residential - 10,000 Watt - NG & LP - Incl Transfer Switch, STOP BRAKE SWITCH 30 Amp FOR WIND TURBINE GENERATOR TRANSFER SWITCH SOLAR , STOP BRAKE SWITCH 50 Amp FOR WIND TURBINE GENERATOR LOAD TRANSFER SWITCH SOLAR, Automatic Transfer Switch, 100 AMP, Generator Standby Power, Generac 200 Amp RTS Transfer Switch, Generators Up To 60 kW RTSX200A3 NEW, Onan 600Amp 480V Generator ATS Automatic Transfer Switch - Worwetz Energy System, RV Auto Line Generator 50A Transfer Switch ATS 5070, GenTran 2026 6-Circuit 20 Amp Generator Transfer Switch, Parallax RV Generator Automatic Transfer Switch 30 Amp, Parallax RV Automatic Generator Transfer Switch 50 Amp,